Specification Sheet
WB-168, WB-208, WB-258, WB-308
Horizontal Water Bath Vaporizer
Horizontal Water Bath Vaporizer
Type | Horizontal Water Bath LPG Vaporizer | ||||
Model Number | WB-168 | WB-208 | WB-258 | WB-308 | |
Capacity | gph | 168 | 208 | 258 | 308 |
kg/h | 322 | 399 | 495 | 585 | |
MMBTU/h | 15.5 | 19.1 | 23.7 | 28.1 | |
kW | 4500 | 5600 | 6900 | 8200 | |
Water Tank Capacity |
165 Gallons (0.625 m3) to Fill Plug |
||||
Burner Type |
European-style compact Forced Draft Power Burner; |
||||
Burner Capacity | MMBTU/h | 0.200 | 0.250 | 0.310 | 0.370 |
kW | 59 | 73 | 91 | 108 | |
Design Temperature | 650 °F (343 °C) | ||||
Design Pressure | 250 PSIG (17.2 bar) | ||||
Manufactured Construction | Vaporizing Tube Conforms to ASME Boiler & Pressure Vessel Code, Section VIII, Division I. Conforms to latest edition of NFPA #58. Power type Burner; Electronic Flame Safeguard; Electronic System Controls with Siemens or Allen-Bradley PLC and Operator Interface with color LCD display and touch screen. First-Outage Monitor (Alarm History with date and time stamp) and graphic trend recording. |
||||
Approvals | Factory Mutual (FM) or Industrial Risk Insurers (IRI). Optional European CE Approval including PED, ATEX, and all other applicable Directives. |
||||
Standard Safety Features
|
|
||||
Liquid Inlet Connection | 1" 300# Raised Face ANSI Flange (Optional DN25 PN40 DIN Flange) | ||||
Liquid Inlet Valve | 250 psi Flanged Direct-Acting Solenoid Valve; with Check Valve Bypass; Globe Valve for Manual Shutoff. | ||||
Vapor Outlet | 2" 300# Raised Face ANSI Flange (Optional DN50 PN40 DIN Flange) | ||||
PLC and Electronic Operator Interface |
|
||||
Electrical Requirement |
220/230VAC 50/60Hz; 15A Circuit; 1-Phase; |
||||
Circuit Protection | Automatic Circuit Breakers with Manual Reset for all AC and DC Circuits; Main Breaker/Disconnect. | ||||
Design Criteria, Vaporizer | Designed and manufactured to comply with the latest edition of NFPA Pamphlet 58; FM approved. European CE Mark available. | ||||
Design Criteria, LPG Heat Exchanger | Designed and manufactured in compliance with ASME Boiler and Pressure Vessel Code Section VIII, Division 1. ASME U-Stamp available. CE-marked vaporizers comply with European PED. |
||||
Design Criteria, Control Panel | General-purpose wiring, compliant with National Electric Code (NEC; NFPA #70). UL-508A available. CE-marked vaporizers comply with all applicable European Directives. | ||||
Mechanical Construction Skid Base |
1/4-inch (6.35mm) Steel Deck Plate on all-welded 4-inch (100mm) Tubular Frame with Cross-Members; Lifting Lugs; mechanically cleaned, primed, and painted (dark-gray, RAL 7043). | ||||
Mechanical Construction, Bath Box |
1/4-inch (6.35mm) all-welded steel walls with internal stiffeners and supports for LPG Heat Exchanger. | ||||
Mechanical Construction, Water Circulating Pump |
Wet-Cartridge Type Hot-Water Circulator installed inside Vaporizer Control Room. Diffuser in Water Bath. | ||||
Mechanical Construction, Insulation |
Mineral Fiber insulation with Aluminum backing on side walls, top plate, and front and rear walls. | ||||
Mechanical Construction, Bath Box Cover |
16-gauge (1.5mm) Sheet Metal, pre-formed, powder-coated (beige RAL 7038). | ||||
Mechanical Construction, Control Room |
16-gauge (1.5mm) Sheet Metal, pre-formed, powder-coated (beige RAL 7038); lockable double-door; louvers, window insert. | ||||
Mechanical Construction, Dimensions |
Overall: 48" (W) x 132" (L) x 110" (H) |
||||
Mechanical Construction, Dimensions |
Overall: 1.22m (W) x 3.35m (L) x 2.79m (H) |
||||
Mechanical Construction, Shipping Weight |
3700 lbs |
||||
Catalog Drawing | Click here for Catalog Drawing (excerpt from Page 6 of Brochure) |